DAQ Upgrade - Installation of TRB, AddOn, Network...

Trigger Distribution

  • RPC: One PECL->LVDS converter on each sector
  • Shower: Same distributor board as RPC
  • TOF: One PECL->LVDS distributor on each sector
  • MDC 3/4: Same as TOF distributor
  • MDC 1/2: One PECL->LVDS distributor on two sectors. Then LVDS connection to FanPW on each sector
  • RICH: own trigger distribution, four LVDS lines from CTS, own LVDS->LVDS distributor board
  • Start, Veto: Connected to TOF-Distributor to have the same jitter on Start and TOF
  • Wall: One PECL-> LVDS distributor

Total: 6 RPC/Shower, 2 MDC12, 6 TOF/MDC34, 1 Wall -> 15 PECL-LVDS-Boards needed;

TrbNet Hubs

Detector Hubs Setup Position
MDC34 1 no Gbe front right corner of mainframe
MDC12 1 no Gbe under right platform, next to MDC power supplies
RPC 2 no Gbe rear right corner of mainframe
TOF 1 no Gbe front right corner of mainframe
Shower 1 no Gbe rear right corner of mainframe
RICH 3 Gbe under right platform, next to MDC power supplies
CTS / Others 1 maybe Gbe in old trigger rack

Total: 10 TRB-Hub2 boards

TRBs

Detector Amount Configuration
RPC 24 with TDC
TOF 7 with TDC
Shower 0 AddOn on RPC-TRB
MDC 0 New MDC Concentratos is a stand-alone board
RICH 0  
Hubs 10 power supply & Etrax only
CTS 2 One board CTS, one for slow control
Forward Wall 3 with TDC
Start/Veto 1 with TDC

Network Switches

Name Detector Datarate Downlinks Uplinks Position
HADSW01 Shower & RPC 1,2,3 45 6x Shower, 1x RPC 05P-18 rear right corner, new 16/4port switch
HADSW02 Shower & RPC 4,5,6 45 6x Shower, 1x RPC 05P-17 rear right corner, new 16/4port switch
HADSW03 MDC12 1,2,3 60 3x MDC 01C-06 under right platform, 12/12port switch
HADSW04 MDC12 4,5,6 60 3x MDC 01C-03 under right platform, 12/12port switch
HADSW05 MDC34 2,3,4, TOF 1-4 60 3x MDC, 4x TOF 1-4 1 front right corner, new 16/4port switch
HADSW06 MDC34 1,5,6 TOF 5-X 60 3x MDC, 3x TOF 5,6,X 1 front right corner, new 16/4port switch
--- RICH 100 3x RICH GbE 01C-05, 01C-07, 01C-04 under right platform, no switch, only media converters
HADSW07 Foward Wall 30 1x FW GbE, 4x TRB 01C-08  
HADSW08 Shower 5,6 100 2x Shower 05Q-20 table, rear right corner
HADSW09 Shower 2,3 100 2x Shower 05Q-19 table, rear right corner
Switch 7 MDC LV et.al. 0 8x MDC Power Supplies 01C-01 above MDC LV power supplies
Switch 8 CTS 5 CTS, other boards on CTS stack 1 on CTS stack
Switch 9 RICH 0 4x Rich / MDC12 SCtrl via Switch 7 RICH TRB stack
Switch 10 - 15 RPC / Shower 0 4x RPC TRB, 1x Hadcon via HADSW01/02 on each sector

Port Usage

HADSW01 (RPC/Shower 1,2,3) (192.168.100.29)

  • Port 1: RPC/Shower sector 1
  • Port 2: RPC/Shower sector 2
  • Port 3: RPC/Shower sector 3
  • Port 9: RPC Hub sector 1,2,3
  • Port 12: Uplink, port on wall 05P-18
  • Port A: Shower sector 1
  • Port B: Shower sector 2 (moved to HADSW09)
  • Port C: Shower sector 3 (moved to HADSW09)

HADSW02 (RPC/Shower 4,5,6) (192.168.100.30)

  • Port 1: RPC/Shower sector 4
  • Port 2: RPC/Shower sector 5
  • Port 3: RPC/Shower sector 6
  • Port 9: RPC Hub sector 4,5,6
  • Port 10: Shower Hub
  • Port 12: Uplink, port on wall 05P-17
  • Port A: Shower sector 4
  • Port B: Shower sector 5 (moved to HADSW08)
  • Port C: Shower sector 6 (moved to HADSW08)

HADSW03 (MDC 1/2 1,2,3)

  • Port 1: MDC1/2 sector 1
  • Port 2: MDC1/2 sector 2
  • Port 3: MDC1/2 sector 3
  • Port 12: Uplink, port 6 on patch panel, 01C-06

HADSW04 (MDC 1/2 4,5,6)

  • Port 1: MDC1/2 sector 4
  • Port 2: MDC1/2 sector 5
  • Port 3: MDC1/2 sector 6
  • Port 12: Uplink, port 3 on patch panel, 01C-03

HADSW05 (MDC 3/4 1,2,3)

  • Port A: MDC1/2 sector 1
  • Port B: MDC1/2 sector 2
  • Port C: MDC1/2 sector 3
  • Port 1: TOF 1
  • Port 2: TOF 2
  • Port 3: TOF 3
  • Port 4: TOF 4
  • Port 8: Mainframe left side
  • Port 9: TOF Hub
  • Port 10: MDC 3/4 Hub
  • Port 12: Uplink, 05Q-18

HADSW06 (MDC 3/4 4,5,6)

  • Port A: MDC1/2 sector 4
  • Port B: MDC1/2 sector 5
  • Port C: MDC1/2 sector 6
  • Port 1: TOF 5
  • Port 2: TOF 6
  • Port 3: TOF X (extra board)
  • Port 12: Uplink, 05Q-16

HADSW07 (Forward Wall)

  • Port A: Forward Wall Hub
  • Port 1: Forward Wall TRB 1
  • Port 2: Forward Wall TRB 2
  • Port 3: Forward Wall TRB 3
  • Port 5: Hub TRB
  • Port 8: High Voltage 1
  • Port 9: haepc06 (expert power control)
  • Port 12: Uplink, 01C-08

HADSW08 (Shower 5,6) (192.168.100.24)

  • Port A: Shower 5
  • Port B: Shower 6

HADSW09 (Shower 2,3) (192.168.100.23)

  • Port A: Shower 2
  • Port B: Shower 3

Switch 7 (Power Supplies)

  • Ports 1 - 11: power supplies
  • Port 12: MDC1/2, RICH slow control
  • Port 24: Uplink, port 1 on patch panel via white switch

TrbNet Hubs

Physical connections. Ports 5 to 16 are mapped to Port 1 to 12 internally.

Central Hub

  • Port 20: CTS
  • Port 18: SCS
  • Port 5: RPC sec. 1 2 3
  • Port 6: RPC sec. 4 5 6
  • Port 7: MDC 1/2
  • Port 8: MDC 3/4
  • Port 9: Forward Wall
  • Port 10: TOF
  • Port 11: Shower
  • Port 12: RICH 1/2
  • Port 13: RICH 3/4
  • Port 14: RICH 5/6

RICH 1,2

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 9: RICH sector 1, segments 0 - 4
  • Port 10 - 14: RICH sector 2, segments 0 - 4

RICH 3,4

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 9: RICH sector 3, segments 0 - 4
  • Port 10 - 14: RICH sector 4, segments 0 - 4

RICH 5,6

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 9: RICH sector 5, segments 0 - 4
  • Port 10 - 14: RICH sector 6, segments 0 - 4

MDC 1,2

  • Port 20: Uplink
  • Port 5 - 10: MDC plane 1/2, sectors 1 to 6

MDC 3,4

  • Port 20: Uplink
  • Port 5 - 10: MDC plane 3/4, sectors 1 to 6

TOF

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 10: TOF sectors 1 to 6
  • Port 11: TOF extra board

RPC 1,2,3

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 8: RPC sector 1, segments 0 - 3
  • Port 9 - 12: RPC sector 2, segments 0 - 3
  • Port 13 - 16: RPC sector 3, segments 0 - 3

RPC 4,5,6

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 8: RPC sector 4, segments 0 - 3
  • Port 9 - 12: RPC sector 5, segments 0 - 3
  • Port 13 - 16: RPC sector 6, segments 0 - 3

Shower

  • Port 20: Uplink
  • Port 5: Shower sector 6
  • Port 6: Shower sector 5
  • Port 7: Shower sector 4
  • Port 8: Shower sector 3
  • Port 9: Shower sector 2
  • Port 10: Shower sector 1

Forward Wall

  • Port 20: Uplink
  • Port 17: GBE
  • Port 5 - 7: Forward Wall TRB 1 - 3

Position of TRB, AddOns, Switches

Here is the list of installations needed, ordered by location. "Lvln" refers to the level in the stack of boards.

  • Behind RPC detector for each sector (height: 6 6 6 12 12)
    • Lvl1 : Ethernet switch (4x TRB, 1x uplink), 48V distribution, Trigger distribution
    • Lvl2 : TRB RPC part3
    • Lvl3 : TRB RPC part2
    • Lvl4 : TRB RPC part1, Shower AddOn
    • Lvl5 : TRB RPC part0, Baseline restorer

  • Rear right corner of mainframe (height: 6 6 6 6)
    • Lvl1 : 48V distributor
    • Lvl2 : RPC hub 1 (sector 1,2,3)
    • Lvl3 : RPC hub 2 (sector 4,5,6)
    • Lvl4 : Shower hub (all sectors)

    • Optical switches (6x Shower, 6x ethernet switch, 3x Hub slow control, 2x uplink)

  • Front left corner of mainframe (height: 6 6 6 6)
    • Lvl1 : Ethernet switch, 48V distribution
    • Lvl2 : MDCAddOn sector 1
    • Lvl3 : MDCAddOn sector 6
    • Lvl4 : MDCAddOn sector 5

  • Front right corner of mainframe (height: 6 6 6 / 6 6 6)
    • Lvl1.0 : 48V distribution
    • Lvl1.1 : MDCAddOn sector 2
    • Lvl1.2 : MDCAddOn sector 3
    • Lvl1.3 : MDCAddOn sector 4

    • Lvl2.1 : Ethernet switch, trigger distributor (TOF)
    • Lvl2.2 : MDC3/4 Hub
    • Lvl2.3 : TOF Hub

    • Optical switch for MDC3/4

  • Beside right platform, right of RICH / MDC 1/2 (height: 6 6 6 6 / 6 6 6 6 / 6 6 6 6)
    • Lvl1.1 : MDCAddOn sector 1
    • Lvl1.2 : MDCAddOn sector 5
    • Lvl1.3 : MDCAddOn sector 6
    • Lvl1.4 : MDC Hub

    • Lvl2.1 : MDCAddOn sector 2
    • Lvl2.2 : MDCAddOn sector 3
    • Lvl2.3 : MDCAddOn sector 4
    • Lvl2.4 : MDC1/2 Hub

    • Lvl3.1 : Ethernet switch, 48V distribution
    • Lvl3.2 : RICH hub sector 1,2
    • Lvl3.3 : RICH hub sector 3,4
    • Lvl3.4 : RICH hub sector 5,6

    • Optical switch for MDC1/2
    • Media Converters for RICH

  • CTS/Start/Veto (height: 6 12 12 12)
    • Lvl1 : Ethernet switch, 48V distribution, Trigger distribution
    • Lvl2 : Central hub with slow control TRB
    • Lvl3 : CTS board
    • Lvl4 : Start/Veto TRB

  • On each TOF sector (height: 12), 7 stacks in total

48V power supply

In total 5 48V power supplies will be used:
  • 2 for RPC (in old Shower rack)
  • 1 for RICH frontends (in MDC LV rack)
  • 1 for RPC, FW & Shower TRBs incl. hubs (in old Shower rack)
  • 1 for all other TRBs (in MDC LV rack)

All 3 RPC/Shower power supplies can be installed in a rack next to the rear part. The other 2 in the rack with MDC power supplies.

Detector Current
RPC 60A (detector) + 20A (TRB)
Shower 5A
TOF 10A
RICH 25A
MDC 5A
Hubs 8A
Others 8A

-- JanMichel - 26 Jan 2010